8.3 Battery Configurations
There are different configurations for different battery types and backup time. Here, the batteries from VISION and
YUASA are selected. The backup times ranges from 1hours to 4hours for 20KVA UPS and from 1hours to 2hours
for 30KVA UPS, because of limitation of CLA power rating.
UPS Backup
time Number of blocks Type of blocks Capacity(10H)
1h 1Ć24 6FM55SGX 52Ah
10kVA 2h 2Ć24 6FM45X 2Ć42Ah
4h 2Ć25 6FM75X 2Ć74.5Ah
1h 24 6FM75X 74.5Ah
15kVA 2h 3Ć24 6FM45X 3Ć42Ah
4h 3Ć25 6FM75X 3Ć74.5Ah
1h 1Ć25 6FM90X 90Ah
20kVA 2h 3Ć25 6FM55X 3Ć52Ah
4h 2Ć26 6FM150X 2Ć144h
1h 2Ć25 6FM75X 2Ć74.5Ah
30kVA
2h 3Ć24 6FM100X 3Ć96Ah
Sheet. 4 the battery configuration with VISION battery
UPS Backup time Number of
blocks Type of blocks Capacity
(10H)
1h 2X24 NPL24-12 2X24AH
10kVA 2h 2Ć26 NPL38-12 2Ć35.3AH
4h 2Ć26 NPL65-12 2Ć60.5Ah
1h 1Ć27 NPL65-12 60.5Ah
15kVA 2h 2Ć24 NPL65-12 2Ć60.5Ah
4h 3Ć26 NPL65-12 3Ć60.5Ah
1h 1Ć27 NPL100-12 92Ah
20kVA 2h 2Ć24 NPL100-12 2Ć92Ah
4h 4Ć26 NPL65-12 4Ć60.5h
1h 3X24 NPL65-12 3Ć60.5Ah
30kVA