American standard unit, flame comes on three times for a bout ten seconds each time then shuts off. wontt stay lit. status light blinks slow no pattern
You have a limit switch that is tripping. I bet it is the flame roll out switch that is very close to the burners. You can bypass this switch to check if it is the one causing the problem by removing the two wires going to it and installing a small jumper wire between them. If the unit starts up, then that's the problem and if not, check all of them. But that's pretty much the only thing it can be. But, you need to double check that the unit is being told to come on and not cutting out intermittently. I doubt it though!