I can run the ups on inverter but i can not establish static switch bypass. could this be a problem with the main processor board? or a specific board in general?
SOURCE: I have a MGE Galaxy UPS and it's giving me an intermittent alarm saying "INV. NOT. SYNC./ AC.BP".
Dear Yared,
The alarm is pretty clear about what is going on. It's a syncing issue between the inverter and your bypass supply.
What you can try is to go to the 'Command Screen' of the UPS and select Resynchronize AC BP.
Best regards,
Ron
Testimonial: "Thank you so much Ron. The alarm has not occurred again. Yared"