The output voltage is 101 volt between la y n, I expeccted 120 volt
There`s two configurations that you need to check.
On UPS display, what voltaje is showing as output voltage?
There`s a chance that it is configured to 200 vac, then the transformer module will convert this to 100/200 vac.
If this is not the situation, probably the error is in the input connection of transformer module.
Battery test failed
This means that the internal battery test failed and that batteries should be replaced.
Power module fault
Pull it out and reseat it. If that don't work then you will have to replace the module