According to the Owner's Manual if the Error Code flashes "06" the O.D. coil Temperature > 175 Deg
F for 2 consecutive minutes. (Heat Pump models only).
The action taken by the unit is Alternate flash set point and error code. Shut unit down for 5 minutes, then try again 2 times, if fails the 3rd time, then shut down unit.:
All of this is can caused by several things:
• Dirty filters
• Dirty coil
• Fan motor failure
• Restricted air flow
• Improper refrigerant charge
• Restriction in refrigerant circuit
The dirty filters, dirty coil and restricted air flow you can troubleshoot and solve yourself. The reaming ones should be handled by a an authorized service technician.
Here's a link to your Owners Manual, that you can download and print for future reference.
http://www.ajmadison.com/ajmadison/itemdocs/92008705_9-07_PTAC_IO_manual.pdf
Hope this helped to to troubleshoot and solve the problem . Please let me know. Thanks.
×