Anonymous Posted on Jul 08, 2017

17 KW Kohler will start and idle but will not step up to proper RPM to run the generator. Is it common for NO gas (Propane) pressure to pass through the regulator when the engine is trying to start. Or does the engine draw the propane that is needed. (There is no-flow through the regulator) Serviceman changed the main circuit board in the unit, and it still would not start and run. Speed sensor checks ok, Throttle Step checks ok.

2 Related Answers

Anonymous

  • 3 Answers
  • Posted on Feb 20, 2010

SOURCE: I have a new Kohler 12kw res generator on propane - backfiring

Is the outside air temp cold. These generators will backfire if it is real cold and if the propane pressure is low. It is suppose to be 11 to 12 inches of water colume at the generator fuel input. drygwals

Ad

Anonymous

  • 2 Answers
  • Posted on Sep 20, 2010

SOURCE: I have a new Kohler 12kw res generator on propane - backfiring

did you put the propane orifis in and unplug the spark wire

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

Generac troubleshooting

please send me more info about this generator I need a model number is this a natural gas or propane I have a neighbor that just had one installed I might be able to get some info from him to help you
0helpful
1answer

WHAT WOULD CAUSE A AUX FAULT ON A KOHLER GENERATOR MODEL 80ROZJ

Aux fault can be many things, if it failed to start you may get it. Try reseting and manually starting. See if it re-occurs while it is running or does it ever start and give error. I have seen this generator by a coolant level sending it is an auxillary fault
0helpful
1answer

I have a Kohler 12 RES home standby generator. Once in a while when the power goes out the generator will start and then immediately shut down with no fault codes. When I flip the control in the unit

Check the inlet fuel pressure, on exervise there is no load, when power is out it is loaded and demands more fuel. Also check for bugs blocking gas regulators vents etc
0helpful
1answer
2helpful
1answer

The monitoring system of our Kohler propane generator has sent a "UU" message. What does this mean as it causes the generator to shut down 10 seconds after starting? Also how can this be...

The monitoring system of our Kohler propane generator has sent a "UU" message. What does this mean as it causes the generator to shut down 10 seconds after starting? Also how can this be corrected?
0helpful
1answer

What is he avrage price of this system

depending on what accessories you get and the fuel type like gas diesel nat gas propane it can run a couple thousand dollars plus the install as well if city permits required it is hard to say hope this helps shop around and have it installed by someone you trust or certified bonded and insured so there is no risk of a home fire good luck.
1helpful
3answers

I have a new Kohler 12kw res generator on propane - backfiring

Is the outside air temp cold. These generators will backfire if it is real cold and if the propane pressure is low. It is suppose to be 11 to 12 inches of water colume at the generator fuel input. drygwals
Not finding what you are looking for?

239 views

Ask a Question

Usually answered in minutes!

Top Kohler Electrical Supplies Experts

Brad Brown

Level 3 Expert

19187 Answers

john h

Level 3 Expert

29494 Answers

ADMIN Andrew
ADMIN Andrew

Level 3 Expert

66955 Answers

Are you a Kohler Electrical Supply Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...