Thanks for your detailed statement as stopped working after water leak.
Water leak due to
It's because of non-maintained air conditioner. Clean airfilter, indoor coil, blower wheel and also drain pan. Insulate freon pipelinesproperly and tightly. After that run the a/c. If still water dripping. Checkindoor f.motor speed. If less replace capacitor. If f.m. is o.k, check gaspressure. If less, there will be ice formation over the coil and water drippingwill be there when it melting. If short of gas, check for leak andrectify. (Unit stopped as coil sensor is activated while ice forming over coil)Thanks. Helpful?