Cannot get the decora 4 way light switch to work - 2 of the 3 switches work but cannot get the 3rd to work. Replacing regular toggle switches which all worked but wiring different for decora switches.

  • Anonymous Dec 23, 2010

    Of the three switches, only one (or none) is a dimmer, correct?
    How does the non-functioning switch behave? Does it have no effect in either postion - that is, if the light is on it won't turn it off, and if it's off it won't turn it on?

×

1 Answer

A

Anonymous

Decora 3-way and 4-way switches do not wire differently than toggle-type switches.
Instructions below are tedious but will accurately guide you to solution.

Let's break down the problem starting with 3-ways.

1) Start with 3-way switches:
Old 3-way switch has 2 brass screws and 1 dark screw
New decora has same color screws.
Wire that went to dark screw on old device must attach to dark screw on decora device.
Other two wires can attach to either brass screw.
Wires that attach to brass screws are travelers ... these wires travel to the 4-way switch.
So there are 2 traveler wires at each 3-way switch.

2) Let's test if 3-way switches are wired correctly by taking 4-way switch out of equation.
We will resolve problem with 4-way switch after 3-ways are correct.

There are 4 wires at the 4-way switch.
These are the 2 traveler wires that arrive from each 3-way switch.

At the 4-way switch, 2 wires arrive in one cable, and 2 wires arrive from another cable.
To say it differently, there are 2 wires from cable1 and 2 wires from cable2.
Connect 1 wire from cable1 to 1 wire from cable2 with a wire nut
Now connect the 2nd wire from cable1 to 2nd wire from cable2 with another wire nut.
So now the traveler wires are connected, and the 4 way switch is out of equation.
Turn on power, and click 3-way switches to see if both switches turn lights on-off in all positions.

Do your 3-way switches work correctly?

3) If 3-ways are not correct, then you have wrong wire connected to dark screw.
First thing to check is if you can identify traveler wire colors by looking at wires at 4-way switch.
Remember, traveler wires at 4-way switch go back to 3-way switch and connect to brass screws on 3-way switch.

4) If you cannot tell traveler wires by looking at 4-way switch, then you can try different combinations until both 3-way switches work.
Or you can test: disconnect wires from one of the 3-way switches. Separate 3 wires for testing. Move other 3-way switch to down position. Turn on power. Test each wire to bare ground wire. Mark wire that lights up. Now move other 3-way to up position. Test each wire to bare ground wire. If same wire lights up each test, then that wire goes to dark screw. If different wire lights up, then mark that wire. The two marked wires are travelers, and they connect to brass screws. Other wire connects to dark screw. Repeat identical test for other 3-way switch.

At this point your 3-way switches will work, if light bubs are not burned out.

5) Last step, the 4 way switch.
Remember from step above, that 2 wires arrive in cable1: These 2 wires connect on one side of 4-way switch. The other 2 wires that arrive in cable2 connect of other side of 4-way switch.

Add a comment if you need more help.

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

How do I wire a 4 way switch in my home

in order to wire a 4 way switch, there needs to be a total of 3 switches working to operate a device/light. you need a 2-wire coming from power source, 3-wire from first switch to 4-way switch then 3-wire to last switch. white wires (neutral) get connected together. Depending on the layout of the switches. i.e where the power comes from and where the switch leg goes to but a basic 4 -way switch is in between 2 other 3-way switches.

6928ae07-fbd3-4cea-b937-54088e9eede4.png

c269cdb0-bf34-4ccd-bf2c-276a65791e3f.png
0helpful
1answer

We have Leviton Decora switches throughout our house. Some of the lights flicker, and have since the house was built 4 yrs ago. When they flicker the switch makes the same sound that it does if, when the...

Several questions here.

1) Lights should not flicker and switch should not make sound (or get unusually warm)
2) You should not have to 'press hard' to get switch to turn off.
3) Are the switches defective. YES. Remove and replace with ordinary toggle switch and see if flickering and sound-making continue. If problems continue, maybe local electrician should assess problem on-site.
4) Press to Release. You are speaking about wires connected on back of switch using 'quick-connects.'
Wire is pushed into a hole where wire is wedged against brass spring and held tight.
To release wire there is usually a hole or slot next to wire. Push small screwdriver into opening. Usually you have to push screwdriver very hard using one hand while other hand holds switch. Then use your additional hand to pull out wire. Or you can clip wire off and then strip back insulation and start fresh on new switch.
5) Builder electricians sometimes buy super cheap brand knock-offs that are not UL rated. Do not think all Leviton products lack quality. Buy new switches at local home center, and new switches will work fine.
6) When replacing switches, pay attention to screw-color that sits next to quick connect. Take a photo before removing all wires.
Screw colors tell electrician how to wire a device, and you can post new question at fixya, or add a comment for specific help.

7) Resources:
http://waterheatertimer.org/How-to-wire-Cooper-277-pilot-light-switch.html
http://waterheatertimer.org/How-to-twist-electric-wire.html

8) Take a moment and rate answer:
And take advantage of fixya expert assistance live.
For a price, expert works with you while you work on electrical switches or any do-it-yourself project.
Fixya is always less expensive than a service call.
0helpful
1answer

How do I hook up a Leviton Decora no 5601... I have a white, a red, and a black wire

Wiring is unclear without more information.

Question posted under 4-way switch.
Wiring sounds like 3-way switch is possible.
And Leviton 5601 is single pole switch.

Add a comment and say what load the switch controls. Load means light, fan, motor, etc.
Say if another switch controls same load.
And include what type of device you are replacing.
Include what screws and screw colors are on old device.

When you add a comment, it sends email, and I will respond to comment.
1helpful
2answers

I just installed a Leviton IP106 Illumatech dimmer switch. It was replacing my existing rotary dimmer switch. The switch is a 3-way wiring job, with another 3-way toggle switch (no dimmer) on the other...

The Leviton IP106 Illumatech dimmer switch must be installed at the switch location where the hot feed exists. From your description your hot feed is at the regular 3-way switch location. Swap locations.
1helpful
2answers

I have a bad decora switch, how can i tell if it i...

In addition to your answer that was given to you. Look at the amp rating on the switch you just removed. It's probably a 20 amp switch (if you already had 12 guage wire in there, and it worked fine), and you're replacing it with a 15 amp. Happens all the time. As far as the answer given you, its fine. The only time you would use a 4-way switch is when it's being operated by two 3-way switches from opposite ends like the gentleman mentioned. I would suggest getting the correct 3-way switch. It just makes things easier. And again, turn OFF the circuit when working on this switch - or anytime you're working on anything electrical. This is a huge Rule-of-Thumb! I've been doing electrical work for over 27 yrs., and I always turn OFF the electricity.  Best of Luck to you, and I hope this is a little added solution to the one you already have. Take care...Jim 
2helpful
1answer

I have two Leviton Decora Motion Activated Light Controls model PR180-1LA that I would like to use at the top and bottom of a stairway. There is only one light that needs to be turned on and off by the...

Unfortunately you cannot use two PR180-1LA's for what you want to do. :-( There is only one correct installation:
One PR180-1LA needs to be installed at the switch box which contains the cable that goes to the light (load). That is a must. One then installs a regular 3-way switch at the switch box which contains the cable with the hot from the breaker (line or source).

If you reverse the sensor location you will need 4 wires between the switches, which is not usual practice, as the bare grounding wire is not permitted to carry current per National Electric Code rules.

If you want a sensor at both locations you need to install a IPP15-1L at the switch box that has the cable going to the light (load). One must then install a IPP0R-1L at the switch box that has the cable with hot from the breaker (line or source).
0helpful
1answer

I have a Leviton Decora five button electronic timer.

You need to have a pair of white wires wirenuted and shoved in the back of the box. White to white, black to the hot and blue to the load on the second black. Some of these have a yellow wire for three way connections.
Not finding what you are looking for?

875 views

Ask a Question

Usually answered in minutes!

Top Leviton Electrical Supplies Experts

john h

Level 3 Expert

29494 Answers

Sean Wright
Sean Wright

Level 3 Expert

2045 Answers

CJ Rock
CJ Rock

Level 3 Expert

4429 Answers

Are you a Leviton Electrical Supply Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...