Ive got a nordic sauna with a 13 amp plug, but after using it for an hour it s blown the fuse ..
Unless you have "Nordic Mini 3" for 240 V, all other types of Nordic sauna are more than 5000 Watt which means that their rated current for 240V is more than 30 A. For 120V it is two times more.
I don't know your type of Nordic, the rating of the fuse and what voltage are you using, but it may be less than the needed rating. Check the rated voltage and current of your sauna heater.
If your voltage is equal to the rated and the rated current of the sauna heater is less than the rating of the blown fuse, you may have short in a part of the heater.