Question about Honeywell Heating & Cooling
Replaced Bryant Thermostat model TSTATBBNB001 with Honeywell model RTH3100C. Old terminals labeled R,G,Y1,W2,W1(O,B),Y2,C. Heat pump wired with Red wire to R, Green wire to G, White wire to W1, Black to C, Yellow to Y1. No other wires used. System is Bryant Heat Pump. Wired new as manual shows with terminals E,AUX,Y,G,O,L,R,B,C. Wired Black to C, Yellow to Y, Green to G, Red to R, and White to Aux. Also put jumper from Aux to E per install manual.. Air cond. seems to work fine. When try to heat the fans come on but blows cold air, no heat!. Am I wired correctly! Thanks
Hello,You forgot to wire the O terminal w1 witch is the reversing valve.It is important to check if old stat is using O or B in witch case B terminal=w1 leaving O unused.
Posted on Apr 21, 2010
Hi there,
Save hours of searching online or wasting money on unnecessary repairs by talking to a 6YA Expert who can help you resolve this issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
Here's a link to this great service
Good luck!
Posted on Jan 02, 2017
Apr 27, 2015 | Computers & Internet
Jun 13, 2013 | Honeywell RTH3100C - Digital Heat Pump...
Apr 21, 2010 | Honeywell Heat/Cool Thermostat
Nov 17, 2009 | Air Purifiers
Jul 24, 2009 | Heating & Cooling
Apr 12, 2009 | Heating & Cooling
Feb 16, 2009 | Honeywell Programmable Thermostat Heater
Dec 20, 2008 | Honeywell Electronic Programmable...
Dec 20, 2008 | Honeywell Programmable Thermostat Heater
Dec 02, 2007 | Heating & Cooling
Nov 13, 2019 | Honeywell Heating & Cooling
439 people viewed this question
Usually answered in minutes!
×