Maytag air conditioner model number m6x08f2a-c keeps turning off after running for a short period of time
If its older than a fee years you may need to clean the outdoor coil. It may be shutting down due to high pressure. I couldn't locate a Google hit so I'm assuming its a window a/c? If so the "air entering" side of the outdoor coil can get dirty and you normally can't see this side until the unit is removed. But you can try to UNPLUG IT FROM THE WALL!!! And the take a water hose and spray from the outside of the outdoor coil. This will try and remove debris. Its always best to remove from window to clean if possible. If the outdoor coil gets dirty it will retain its heat instead of rejecting it to the atmosphere, and heat retension will increase freon pressure causing a high pressure/temperature sensor/switch to open.
Unit turn off inmediatly after turning it on
There is a low freon pressure switch in the system. A small amount of freon will show enough pressure to start the unit. As soon as the compressor starts the low side pressure (where the switch is) drops and shuts the unit off.
The digital temperature indicator is
I suggest that you try turning the unit off, unplugging it, and leaving it turned off for a couple of minutes. Sometimes these appliances can be reset by turning them off, waiting, then turning them back on. It's similar to rebooting a computer when it's hung-up.