My TSSU 60 16 is leaking water insie the cabinet.
Call me, I'm not expensive ;). Seriously, the drain tubes are clogged. Unplug unit and get a flexible piece of electrical wire. The drain tubes terminate near the compressor and usually drain in pan under there. The most common clogs are at the elbow and tee connectors. Good luck! :)
6/27/2015 2:37:01 AM •
True...
•
Answered
on Jun 27, 2015
How to properly install t-stat on TSSU-72-30M-B
The same you remove the old one the new one goes on. Be sure to inscert to sensing bulb in the copper tube in the evap section. 1/4"nut driver and a phillips screw driver
6/27/2015 2:33:07 AM •
True...
•
Answered
on Jun 27, 2015
Will not stop running
Are you referring to the compressor not shutting off down below or the evaporator fan inside the cooling area not shutting off? Evaporator fan always runs the compressor is controlled by the thermostat you could have a bad thermostat if the compressor never shuts off.
Gdm 45 with new thermostat goes down to 28 degrees and compresor does not shut down
If the new thermostat sensor is secure and where it belongs, it has the wrong charge in the system. That cooler takes a critical charge. The factory charge is in ounces if refrigerant. The system needs to be evacuated completely with a vacuum pump and recharged with an accurate scale that weighs in ounces. That will solve your problem. A refrigeration tech carries the necessary tools that an hvac tech doesn't. Hope this helps and good luck.