Hello Chuck;
My name is Peter. I am a retired field service refrigeration technician.
It is good news that your compressor is running. It is running to maintain the set cooling temperature.
The problem is your unit is not getting rid of the system heat.
You have a bad condenser fan motor and plugged up condensing coil.
Could be bad condenser fan motor or bad start components for compressor
SOURCE: Need replace compressor 1449SCAdo you have the
Here's a manual for your unit series. You can contact the manufacturer directly by calling 1-800-621-8560 to verify the correct compressor for your particular unitand model. See page 16 of the manual at the link below for models and replacement part numbers, including the compressor.
http://download.partstown.com/is-bin/intershop.static/WFS/Reedy-PartsTown-Site/-/en_US/manuals/4149_spm.pdf
Hope you found this very helpful and best regards!
SOURCE: Randell 9601/Aspera compressor replacment?
I searched till I found a Randell vendor in our state. They had the answers I needed.