P8-Abnormality in outdoor unit.
1.Wrong wiring of indoor/outdoor
connecting wire.......................Check the indoor/outdoor connecting wire.
2) Reversed phase......Change the connection of electric wiring.
3) Protection device is working........ Check the protection device.(LP,HP)
4) Damaged outdoor coil thermistor.....Measure the resistance of the outdoor coil thermistor.If the resistance is normal, replace the outdoor controller board.
5) Check out door coil is cleaned. If not do it.
thanks.