The 250 MUST have the condensate line connected. EC comes from gas supply problems and CO2 levels not being adjusted. LP units require 3/4" smooth gas pipe or 1" corrugated pipe minimum size. The LP regulator needs to be turned up to about 13 inches of water column and with all the gas appliances on, measure no less than 11 inches of water column. The CO2 levels must be measured by a qualified gas technician with a calibrated (with in 6 months) CO2 analyzer.