Alarm error #191 comes from a battery test, where batteries are put under load for 25 seconds. (If the alarm is unexpected, you might have enabled the periodic 30-day battery test.)
#191 is test failure for battery internal resistance. So, need to locate and replace the bad battery, then run the battery test manually. If batteries are good, make sure no battery connector is corroded or loose.
Powerware was purchased by Eaton and they continue to provide support for all Powerware products. In the U.S. call Toll Free: 1 800 843 9433 (International: +1 919 871 1800) or e-mail: [email protected]. They can help you out with the password. The 9330 manuals and documentation are located here: http://powerquality.eaton.com/Products-services/legacy/9330-info.asp
×