Compressor tries to start, then cuts out, continues trying every 20-30 seconds. Worked fine for first two days then the problem started.
Fan works fine.
There are Five Main reasons that this will happen
1 - A bad run capacitor (silver or metal capacitor)
It’s either shorted, grounded or open.
If it’s shorted a lot of times it will bulge out, (sometimes slightly)
2 - A bad start kit ( plastic capacitor and Relay connected to it )
The capacitor is either shorted or open
The relay either has an open coil between terminals #1 and #5
Or the relay is stuck.
Any time you change the capacitor or relay you should change
the other, especially if they are over a year old.
3 - A loose, burnt or disconnected wire
4 - Wired wrong
5 Compressor is locked up
So I just had this happen with my Frigidaire fad704dwd dehumidifier. I went to basement and heard it running and sounded off. The compressor was running fan was off which is bad and humidity said 30. I then pushed the off button and it stayed running. I was able to fix it. To make long story short it was a bad ground. I took the plastic back, sides, and front off. There was a green ground (main ground) and Green/yellow ground (fan ground) on the front coil with a bunch of rust. Removed the grounds connected them both together and cleaned the surface area and used a new stainless screw nut and screw to remount the wires to evaporator coil. Everything started working fine after that and I put it back together. Good Luck