SOURCE: Error code E9
High pitched noise is from a very high CO2 level. Adjust the gas pressure to stay above 11" w.c. and have a gas technician with a calibrated CO2 analyzer adjust the CO2 levels.
SOURCE: the led panel on the
C6 - compressor run current high
- check [resistance of] compressor windings all equal 1 to 4 ohms
- check [resistance] to earth 50 Mohm minimum
- check run current
I'd also check the motor capacitor(s) , In maximum, it is due to weak capacitor. Replace and try.
SOURCE: Tengo un split elctrolux que esta marcando el
desconectalo de la corriente un rato y conectalo de vuelta aver si asi se hace reset .