SOURCE: Same problem, generator kicked in after power outage,
At the point the transfer switchis suppose to transfer put a dc volt meter across terminals 23 and 194 in the transfer if you do not show 12VDC. Then you have a relay hanging upon the PCB board in the generator, need to replace board. If you are showing 12VDC and the switch is not transferring the problem is in the switch itself.