I have a EATON EX RT 11 that shows ;DC BUS FAILURE - 1CM15046 V02' error on screen. What causes this error? How can this be repaired? Unit is out of warranty

The UPS when started automatically go to bypass mode, when i push 'ON' it will shut down.

  • Mustafa Ali
    Mustafa Ali Feb 22, 2015

    when i switch from bypass to normal, the normal power breaker use to trip. in the attached pic, the big fuse (100 A) found tripp.



×

2 Answers

victor vilca figueroa

Level 1:

An expert who has achieved level 1.

Habit-Forming:

Visited the website for 3 consecutive days.

New Friend:

An expert that has 1 follower.

Welcome Back:

Visited the website for 2 consecutive days.

  • Contributor 1 Answer
  • Posted on Mar 06, 2018
victor vilca figueroa
Contributor
Level 1:

An expert who has achieved level 1.

Habit-Forming:

Visited the website for 3 consecutive days.

New Friend:

An expert that has 1 follower.

Welcome Back:

Visited the website for 2 consecutive days.

Joined: Mar 06, 2018
Answers
1
Questions
1
Helped
1627
Points
3

I HAVE THE CODE 1CKI46013 / V00D ... HELP ME PLEASE!!

Gruber Power Services

Level 2:

An expert who has achieved level 2 by getting 100 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Mentor:

An expert who has written 3 tips or uploaded 2 video tips.

  • Expert 176 Answers
  • Posted on Mar 02, 2015
Gruber Power Services
Expert
Level 2:

An expert who has achieved level 2 by getting 100 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Mentor:

An expert who has written 3 tips or uploaded 2 video tips.

Joined: Aug 24, 2011
Answers
176
Questions
3
Helped
95467
Points
221

Replace your batteries

Ad

2 Related Answers

Vassilis Chamaidis

  • 25 Answers
  • Posted on Feb 05, 2008

SOURCE: Powerware 9120 DC Bus Fault Problem.

there is a 100uf/63v capacitor near the IRF630 fet. You need to replace this in order to fix this error. Along there is also a 2200uf/16v capacitor. It is a good idea to change the both at the same time.

Ad

Anonymous

  • 2 Answers
  • Posted on Jul 01, 2011

SOURCE: Eaton EX RT 11, Windows

Matias,
Try using the Intelligent Power Software Suite (IPSS):
http://powerquality.eaton.com/Products-services/Power-Management/Software.asp
If you are trying to monitor the UPS, use Intelligent Power Manager (IPM). If you are trying to shutdown the Virtual Machine safely, use Intelligent Power Protector (IPP).

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

I have Fujitsu AOTG54LATL showing er11 I have replaced pcb and the two dc fan motors on the outdoor unit Still showing erll

Error code e11 is a communications error. The causes listed in the manual for the outdoor unit are:
1) Connection failure.
2) External cause
3) Main PCB failure.
4) Active filter module failure.
5) Transistor PCB (IPM) failure.
6) Filter PCB failure
7) Outdoor unit Fan motor failure

For the indoor unit the listed causes are:
1. Connection failure
2. External cause
3. Controller PCB failure

With any luck you will have a wiring problem(loose/broken wire). Unfortunately it is more likely to be the Main PCB. Good luck!
0helpful
1answer

HI everyone I've got several UPS Eaton EX 3000 installed in solar farms and ALL of them are malfunction

call the ups engineers for an answer to the problem when connected to solar power
there may be a problem in that solar panels produce various voltages during the day ( depending on the cloud coverage ) and the ups requires a reasonably steady input voltage to operate properly
I have found the eaton ups product to reliable so the suggestion to talk with the engineers to ensure that the system is compatible with the solar set up would be to your advantage
0helpful
1answer

The output voltage is 101 volt between la y n, I expeccted 120 volt

There`s two configurations that you need to check.
On UPS display, what voltaje is showing as output voltage?
There`s a chance that it is configured to 200 vac, then the transformer module will convert this to 100/200 vac.
If this is not the situation, probably the error is in the input connection of transformer module.
0helpful
1answer

DC Bus Fault Error

Dc bus error is from charger o maybe inverter
0helpful
1answer

DC Bus Low

This could be because of bad batteries or you need to adjust the float voltage. First replace batteries
0helpful
2answers

Eaton EX RT 11, Windows 2008 server, in a VMware senario. PSP can't connect tu the UPS. Thanks in advance, Matias.

Matias,
Try using the Intelligent Power Software Suite (IPSS):
http://powerquality.eaton.com/Products-services/Power-Management/Software.asp
If you are trying to monitor the UPS, use Intelligent Power Manager (IPM). If you are trying to shutdown the Virtual Machine safely, use Intelligent Power Protector (IPP).
0helpful
2answers

Is the fuse in a powerware 9135 user replaceble

There are numerous fuses (rectifier, inverter, charger, battery) on the 9135 that are located internal to the unit and not readily accessible to the user. Generally a blown fuse is accompanied by another component failure which caused the fuse to blow in the first place. As a result, additional troubleshooting and testing is usually required to identify the root cause of the failure. This of course leads to soliciting the services of a technician who has access to the schematics, test equipment, and parts to initiate a repair. Without the schematics, it's like working in the dark. For complete support, please contact Eaton (Eaton bought Powerware so now it's the Eaton 9135):

Toll Free: 1 800 356 5737
E-mail: [email protected]

www.eaton.com/9135

62helpful
11answers

Powerware 9120 DC Bus Fault Problem.

there is a 100uf/63v capacitor near the IRF630 fet. You need to replace this in order to fix this error. Along there is also a 2200uf/16v capacitor. It is a good idea to change the both at the same time.
Not finding what you are looking for?

1,637 views

Ask a Question

Usually answered in minutes!

Top Eaton Computers & Internet Experts

Ngoro

Level 3 Expert

3523 Answers

Brad Brown

Level 3 Expert

19187 Answers

NOEL
NOEL

Level 3 Expert

8606 Answers

Are you an Eaton Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...