The UPS when started automatically go to bypass mode, when i push 'ON' it will shut down.
SOURCE: Powerware 9120 DC Bus Fault Problem.
there is a 100uf/63v capacitor near the IRF630 fet. You need to replace this in order to fix this error. Along there is also a 2200uf/16v capacitor. It is a good idea to change the both at the same time.
SOURCE: Eaton EX RT 11, Windows
Matias,
Try using the Intelligent Power Software Suite (IPSS):
http://powerquality.eaton.com/Products-services/Power-Management/Software.asp
If you are trying to monitor the UPS, use Intelligent Power Manager (IPM). If you are trying to shutdown the Virtual Machine safely, use Intelligent Power Protector (IPP).
Toll Free: 1 800 356 5737
E-mail: [email protected]
1,637 views
Usually answered in minutes!
when i switch from bypass to normal, the normal power breaker use to trip. in the attached pic, the big fuse (100 A) found tripp.
×