Are you talking about the small 3 or 5 amp fuse in the furnace? If you are then the control voltage circuit to the condenser is shorted, Maybe dogs or rodents chewing it or the insulation is cut by a sharp piece of metal. Sometimes the contactor will go bad and cause the small fuse in furnace to blow. Look for the simple things first, like control wires shorted. Make sure the yellow wire from the thermostat goes to the outside unit and not to the common.