Anonymous Posted on Aug 16, 2013

I have a Guardian RV 3600 watt generator than wont run more than a few seconds. I have to hold my hand over the breather to get it to fire then as soon as it revs up it shuts off.

1 Answer

ray012965

Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Master:

An expert who has achieved Level 3.

  • Master 453 Answers
  • Posted on Aug 17, 2013
ray012965
Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Master:

An expert who has achieved Level 3.

Joined: Oct 31, 2010
Answers
453
Questions
0
Helped
166672
Points
1016

Carburetor restricted due to long time storage drop carb fuel bowl unscrew the jet and pull down the fuel tube clean them and your generator should run much much better

3 Related Answers

Anonymous

  • 1 Answer
  • Posted on Apr 15, 2009

SOURCE: guardian primepact 50g rv gen starts for 2 sec then shuts down

This story ends with bad gas and silicone in the gen tank

Ad
mamicheddy

mamicheddy

  • 79 Answers
  • Posted on May 07, 2009

SOURCE: I have a 7500 watt guardian rv generator and it is

Before starting the genset remove the air filter and check the throttle plate on the carberator, it should be closed. If it is opened, then you choke coil is worn out and needs to be replaced.

mamicheddy

mamicheddy

  • 79 Answers
  • Posted on May 19, 2009

SOURCE: guardian rv generator

Your control board is faulty. Try to power up the ingnition coil as well as your fuel pump. If this does not get the engine running then you have major engine problems.

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

It back fires

If it backfires, check for manifold leaks, fuel mixture is too lean, timing is off, make sure it isn't spitting liquid into the cylinders and the LP is the right pressure, and the vapour coil is working
1helpful
1answer

My generac 40g rv generator will start fine but no power. I noticed that when it starts the microwave will power up for just a second. I can turn the generator off and on a couple of times and then it will...

It may be demagnetised. If you turn off the generator before unplugging the load this may happened. Try to put a strong magnet (like those from loudspeakers) in contact with the body of alternator. I do this in the past and it work.If you do not know how to do this ask an electrician, he can help you .
1helpful
1answer

Generator starts with and runs great, but theres no current on my toy hauler

Johnny,

If generators are not used regularly, they need the their magnetic field to be charged (or flashed). This can be done by plugging an electric motor into the socket while the generator is running and spin the motor by hand. The hand-spun motor will push some electric current back into the generator and magnetize it enough to start it.

Look in the manual. There is likely something about field flashing the magnetic field2.gif. The easiest way to do this is to.
1) start the generator
2) plug an electric drill into the generator (without drill bit)
3) make sure drill is set to forward direction (if a reversable drill.
4) pull the trigger on the drill.
5) If the drill does not start, spin the drill's chuck clockwise (When looking down at the chuck from the drill bit end). Spin counter-clockwise if holding it like a pistol and pointing away from yourself.
6) Do this several times (hard) until the the generator will kick in and suddenly make the drill spin at full speed.
Be careful not to drop the drill or poke someone with it as you celebrate success.
1helpful
2answers

Coleman 7300 rooftop air conditionor wont operate

When they sit allot - sometimes the fan will stick.. Take the cover off,, turn it on and see if the fan is stuck.. Spin it by hand to free it up..
0helpful
1answer

Guardian rv generator

Your control board is faulty. Try to power up the ingnition coil as well as your fuel pump. If this does not get the engine running then you have major engine problems.
0helpful
1answer

I have a 7500 watt guardian rv generator and it is difficult to start if not used on very regular basis. It cranks but will not fire. If I go out and manually fool with the choke it starts. Obviously it is...

Before starting the genset remove the air filter and check the throttle plate on the carberator, it should be closed. If it is opened, then you choke coil is worn out and needs to be replaced.
0helpful
1answer
0helpful
1answer

Have a 16k propane guardian generator have to manually start and

Is this an RV generator?

If you have to really choke an LP engine but it runs more or less normally once started you need to troubleshoot the demand regulator and the fuel supply lines (look for air leaks). I'd also check the fuel inlet pressure before the demand regulator.

Rate me,
Carl
Not finding what you are looking for?

566 views

Ask a Question

Usually answered in minutes!

Top Guardian Electrical Supplies Experts

ADMIN Andrew
ADMIN Andrew

Level 3 Expert

66855 Answers

Kardoc

Level 3 Expert

7503 Answers

CJ Rock
CJ Rock

Level 3 Expert

4429 Answers

Are you a Guardian Electrical Supply Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...