Copy following link for Hagar timer wiring diagrams and to identify timer model:
http://waterheatertimer.org/How-to-program-Hagar-timer.html
Gene
If you need further help, I’m available over the phone at https://www.6ya.com/expert/gene_9f0ef4df2f9897e7
Copy following links for installations:
http://waterheatertimer.org/How-to-program-Hagar-timer.html#wire
http://waterheatertimer.org/images/EH-010-timer-wiring2.jpg
http://waterheatertimer.org/images/EH-010-timer-wiring.jpg
http://waterheatertimer.org/How-to-install-3-phase-timer.html
EH 010 timer is rated 16 amp max.
Typically this timer is connected to 12-14 gauge wire
Typical 3-phase 7.5 Hp motor draws 22 amps at 230volt and probably connected to 30-40 amp breaker and size 10-6 wire.
Timer and wire to timer must be fuse-protected with 15a bus fuse or line fuse or fuse block, and cannot be directly connected to 30-40 amp line.
Add comment as needed.
If you need further help, I’m available over the phone at https://www.6ya.com/expert/gene_9f0ef4df2f9897e7
1,109 views
Usually answered in minutes!
×