Says overcranck
Typically caused by the fuel line (LP or Natural Gas) having a lot of air in it. Was your generator just installed, or was there any work done to the gas line of the building / generator? Consult local gas contractor / propane dealer / gas company for assistance in purging the fuel line.
A low battery can also cause this as well as the generator is not able to come up to starting speed quick enough. Try placing a stand alone battery charger on the generator and charge the battery. Also check the air filter as well.
OverCrank condition occurs when generator tries to start itself, or be manually started, and the starter spends too much time turning.
This can also indicate failure of the control board. This will need the expertise of generac technician. Call 1-888-GENERAC (1-888-436-3722)
M-F 7am-6pm Central