Diesel mixed with oil in the sump

After running the generator(40kva-perkins), oil pressure falls from 4 to 2 bar while oil level when checked in cold condition found to be too high and oil diluted, smelling of diesel within.

3 Answers

Anonymous

Level 1:

An expert who has achieved level 1.

Corporal:

An expert that hasĀ over 10 points.

Problem Solver:

An expert who has answered 5 questions.

  • Contributor 11 Answers
  • Posted on Mar 21, 2009
Anonymous
Contributor
Level 1:

An expert who has achieved level 1.

Corporal:

An expert that hasĀ over 10 points.

Problem Solver:

An expert who has answered 5 questions.

Joined: Mar 21, 2009
Answers
11
Questions
0
Helped
4974
Points
12

You run again the generator but before running, check & mark the oil level. Then stop the generator & wait until the oil settle to the bottom of oil pan. Check the oil level again & if the oil level is higher than the marking before that's means you have an engine gasket leak.You need to replace that gasket.

sherlywang

Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that gotĀ 10 achievements.

MVP:

An expert that gotĀ 5 achievements.

Master:

An expert who has achieved Level 3.

  • Master 428 Answers
  • Posted on Dec 18, 2018
sherlywang
Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that gotĀ 10 achievements.

MVP:

An expert that gotĀ 5 achievements.

Master:

An expert who has achieved Level 3.

Joined: Oct 20, 2017
Answers
428
Questions
0
Helped
198383
Points
1063
Ad

Anonymous

Level 1:

An expert who has achieved level 1.

New Friend:

An expert that has 1 follower.

Corporal:

An expert that hasĀ over 10 points.

Mayor:

An expert whose answer gotĀ voted for 2 times.

  • Contributor 8 Answers
  • Posted on Jun 03, 2011
Anonymous
Contributor
Level 1:

An expert who has achieved level 1.

New Friend:

An expert that has 1 follower.

Corporal:

An expert that hasĀ over 10 points.

Mayor:

An expert whose answer gotĀ voted for 2 times.

Joined: Jun 02, 2011
Answers
8
Questions
0
Helped
6483
Points
10

You should check your injector seals

  • Mk Ling
    Mk Ling Apr 13, 2015

    you should check your fuel transfer pump or fuel pump seal.

×

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

I need the workshop manual of perkins england 2332/1800 diesel engine of genset generator Olympia Gep150 controlled by Fg wilson uk.best regards

We are Perkins diesel generator OEM and can provide 22KW to 1800KW Perkins diesel generator including open type,silent type and container type genset. Each genset has its user's manual.

Normal starting procedure of Perkins Generator set

1. As far as possible do not start the generator set under load conditions.

2. Transfer the key switch to the starting (STAR) position. The engine should start immediately.

3. After the engine starts, return the key switch to the running (RUN) position. If the engine has not started after 10 seconds, turn the key switch back into operation and (RUN) for 10 seconds. Then repeat steps 2 and 3. If the engine is still unable to start after three attempts, please find out why.

4. After engine starts, follow steps 4.a and 4.b.

A. Check the oil pressure.
B. Check the machine for leaks.
C. Make sure the battery is charged.
D. After running the engine for five minutes, check the generator monitoring system. Make sure the engine works properly before loading.

Note: do not use ether-like spray starting aids in cold weather. Otherwise, it could lead to explosion and personal injury.

The use of water jacket heaters or extra battery capacity improves the machine's start-ability below 10 ?.

Methods for checking and cleaning the core of the rear cooler of Perkins generator set

Check for damage, corrosion, dirt, grease, insect stains, leaves, oil and other debris on the cooler. Clean the cooler if necessary.

https://www.dieselgeneratortech.com/generator-sets/Instruction-for-Perkins-Generator-Set-Maintenance.html
0helpful
2answers

What size generator do I need to run a 10 hp motor

on the plate attached to the motor you will find several important items
one is the wattage of the motor
this is the maximum wattage that the motor uses when under load
the gen set will need to be at least 30% bigger than that figure
next there will the number of phases that the motor is
it will read as 1 ph or 3ph
If it is 1ph that is a single phase motor and will ru from a single phase gen set
however if it is 3ph you will need a 3ph gen set to run the motor
As most single phase motors are limited to around 5hp I would be very sure that the motor is not 3ph
specialist advice from an accredited electrician or electrical motor shop is recommended before buying a gen set. as if you need 3ph the gen sets become expensive.
0helpful
2answers

Perkins engine 40kva , the engine is do in overheating ever time and have change the gaskt two tax why

Make sure all of the vents, on the engine are free of dirt. Check carb adjustment and adjust as needed
0helpful
2answers

Perkins engine

Check oil is correct grade and topped up. If OK overhaul engine.
Jan 27, 2014 • Garden
0helpful
2answers

Pramac 25 kva perkins encl diesel genset will not start red light on triangle on check list

Hello. Maybe you have solved your problems. But I still want to share the helpful article to you. https://www.dieselgeneratortech.com/diesel-generators/why-diesel-generator-fail-to-start.html

We are Perkins diesel generator OEM. Can provide 22KW to 2200KW diesel generator set with Perkins engine. https://www.dieselgeneratortech.com/perkins

perkins diesel generators-n5v1fnwbur1qlbncsxenjidv-1-0.jpg
0helpful
1answer

Perkins 20 kva diesel generator runs and stops in about 2 minutes.alternator failure is displayed on screen.

Ensure any engine control switch is set to the run position, with the load disengaged. Manually set the air shut off valve (if fitted) to the run position (see Fig. 18), Turn the key switch to the start position, which will energize the solenoid allowing the engine to crank over for a few seconds then start.

Check the instrument panel is showing normal running oil pressure, and the ammeter for charge to the engine batteries.
Allow the engine to run for five minutes checking the instruments are reading correctly. Stop the engine and check the oil and coolant levels, replenish if necessary.


https://www.dieselgeneratortech.com/generator-sets/normal-starting-procedure-of-Perkins-generator-set.html
0helpful
2answers

Perkins generator stop and indicate low oil pressure?

If the oil level is correct then you might be up for an oil pump. Some engines have an automatic cut-out for low oil pressure or high temperature as a safety mechanism to protect the engine from massive damage.
2helpful
4answers

Its 230kvaperkins generator it starts normally,but after thirty minutes it shuts dawn automatically indicating low frequency

Low frequency means the RPM of the motor has fallen off.

Check your fuel is NOT contaminated or fuel filters plugged.

Further tests should focus on the govenor system. Possibly it fails when engine gets hot. the frequency is directly proportional to the engine speed.
5helpful
5answers

MY Perkins generator 2300 series crank but can not start

I take it it's diesel. Have you renewed filters? Bleed fuel system Make sure there is plenty of diesel flowing out of tank (pipe not blocked) Check lift pump working
0helpful
4answers

Diesel generator runs for short time then shuts down. it is a onan 7.5 & runs off of the motor home fuel tank

More than likely a safety control circuit on startup. Either high water temp, low oil pressure, or over rev condition. If not any of the above quite possibly the integratrated generator/engine control circuit board.
Allan
Not finding what you are looking for?

805 views

Ask a Question

Usually answered in minutes!

Top Pramac Electrical Supplies Experts

littlewheel

Level 2 Expert

122 Answers

Ngoro

Level 3 Expert

3521 Answers

john h

Level 3 Expert

29494 Answers

Are you a Pramac Electrical Supply Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...