SOURCE: Powerware 9120 DC Bus Fault Problem.
there is a 100uf/63v capacitor near the IRF630 fet. You need to replace this in order to fix this error. Along there is also a 2200uf/16v capacitor. It is a good idea to change the both at the same time.
SOURCE: Powerware 9120. 1500i UPS
You can download the manual and other literature at
http://www.powerware.com/EMEA/UPS/9120_info.asp
The contacts for support in India are found at
http://www.powerware.com/India/Service_Support/IN_Office_Contact.asp
They offer a battery monitoring software package, at
http://www.powerware.com/India/Service_Support/IN_Battery_Services.asp
You can email support at http://www.powerware.com/pp/Check.asp?key=code1
Good luck
SOURCE: powerware ups mod #PW9120100i
You have to turn socket of ups power cord 180 degrees, because the ups is measuring voltage between ground and ac-line.
SOURCE: I have a Powerware 9120 2000 UPS battery failure message
Hi,
After you replaced the batteries did you perform a manual battery test?
If not do so.
Regards
Alan Hood