Charging of the battery is ok. All tests show no failures, but if the unit is disconnected from the power source, all outputs are zero. But the O/P Load is showing 80%!
SOURCE: 9120 Battery Failure
sounds like inverter is unhappy(causing the input fuse to blow. maybe, just maybe, this Powerware 9120 has given up the ghost? The inverter can short for a variety of reasons. Try to take out the battery completely, and run it as just a power conditioner. If that works, then you have an unhappy inverter in there.
SOURCE: I have a Powerware 9120 2000 UPS battery failure message
Hi,
After you replaced the batteries did you perform a manual battery test?
If not do so.
Regards
Alan Hood
ami-man
UK
SOURCE: replacement fans for powerware 9120
9120 fans are rare and uncommon, for alternate solution just replaced the bearing of the fan.