Kohler 17 kW Emergency Power System - 17RES-L - Page 7 Questions & Answers
Kohler 40 kw adc controls troubleshooting
wow intermittants are tough to find , the only way ive ever been sucessfull at it is to temp bypass each sensor (lie to controller) to see if it continues to run ,I do not recomend leaving any thing bypassed and not physicaly monitoring it ,
this temp bypassing is for only the most experienced techs that know normal state of sensors and can simultate them with off machine items
1/30/2015 3:12:31 AM •
Kohler...
•
Answered
on Jan 30, 2015
Why does my generator start constantly?
if a lightning strike was anyplace close (30 yds) it's a safe bet your gonna have to replace the control board in generator also Id have a qualifyed tech ck out your auto transfer switch ,I bet he''ll find that you fried your coils on your switch too , do that before changing control board cus if ya hook up a new one to a bad coil ya just bought two of them
6/4/2014 11:32:42 PM •
Kohler...
•
Answered
on Jun 04, 2014
Kohler 6eod
Under voltage would be low output voltage from the generator power head. Verify that the motor is funning at full speed to check the output voltage.
Low battery is telling you that the starting battery has low voltage. This could be because the battery is bad or that the alternator is not charging the battery
5/23/2014 5:58:43 PM •
Kohler...
•
Answered
on May 23, 2014