Powerware 9120 UPS System - Answered Questions & Fixed issues
I have a powerware 9120
Did your UPS display "Battery disconnected" or did it display "Battery Failure"? If it was "Battery Failure", for some reason the Powerware 9120 will take almost 18 hours after plugging in to power after battery replacement to correct the Battery Failure indication. Charger has to charge up the batteries, followed by an automatic battery test by the UPS. If the indication was "Battery Disconnected", you will need to check the internal fuses to see if they are blown. If the UPS keeps blowing fuses, it will require a board repair.
Powerware 9120 DC Bus Fault Problem.
there is a 100uf/63v capacitor near the IRF630 fet. You need to replace this in order to fix this error. Along there is also a 2200uf/16v capacitor. It is a good idea to change the both at the same time.
How a 20kva circiut diagram looks
You will have very little benefit from a schedule.
All UPS are structured similarly.
A rectifier, an inverter.
A battery charger, a bypass ...
Powerware 9120 batt disconnected
Hi Anonymous,
I want to help you with your question, but I need more information from you. Are the batteries new? If you did recently replace the batteries in the cartridge, did you check the connections and make sure contact as being made?
Let me know!
Daniel •
[email protected] • Power & Systems Innovations • 800.260.2259 • www.psihq.com
Powerware5115 will not switch on
A weak or dead battery pack its the main reason of a unresponsive/good health UPS, but never forget to test the electric cord, the fuse and the protective relay.first, this sounds too simple, but thats a common fault.
Battery pack must have at least 5 volts with half amp of current to power up the UPS internal relays, giving electric power to the main switch.
To rise the 12/24 DC volts to 115/120 AC volts, the UPS uses some electronic components (semiconductors) called MOSFETS , and sometimes, blown (browned) MOSFETS on the electric board are the most desastrous cause of a unresponsive (completely dead) or faulty UPS. (I remember that some time ago I see a TRIPP LITE SMART 1500LCD UPS with twelve blown MOSFETS, when happened, that kind of fault must be saw like a little volcano!).
If you know how to take all the safety electric measures, and how to use a portable voltmeter, you can test the voltage/amperage on the battery pack, the electric cord and the replaceable fuse (if has any). Basic and intermediate electronic knowledge is necessary to test MOSFETS and other electronic components on the circuit board.