Kohler RXT-JFNC-0200A-QS 200 Amp Indoor/Outdoor Automatic Transfer Swi - Page 7 Questions & Answers
Why does my generator start constantly?
if a lightning strike was anyplace close (30 yds) it's a safe bet your gonna have to replace the control board in generator also Id have a qualifyed tech ck out your auto transfer switch ,I bet he''ll find that you fried your coils on your switch too , do that before changing control board cus if ya hook up a new one to a bad coil ya just bought two of them
6/4/2014 11:32:42 PM •
Kohler...
•
Answered
on Jun 04, 2014
Kohler 6eod
Under voltage would be low output voltage from the generator power head. Verify that the motor is funning at full speed to check the output voltage.
Low battery is telling you that the starting battery has low voltage. This could be because the battery is bad or that the alternator is not charging the battery
5/23/2014 5:58:43 PM •
Kohler...
•
Answered
on May 23, 2014
First start up
Try disconencting the remote start wires between the transfer switch and the generator, if ot still does it you have a bad control board. If it stops, then check the transfer switch for correct wiring of utility and generator power wires, also check with an ohm meter if the run contacts in the transfer switch are closed, that would indicate loss of sensing, or bad board
12/1/2013 10:51:28 PM •
Kohler...
•
Answered
on Dec 01, 2013