ROBINAIR 347002K WON'T INJECT OIL I HAVE A ROBINAIR COOLTECH 700 MODEL 347002K. THE OIL INJECT DOES NOT WORK, IT WAS WORKING UNTIL OIL INJECT WAS USED WITH VALVES IN THE RECOVER/VACUUM SETTING. PAG ...
Question about Robinair Measuring Tools & Sensors
When under vacuum down machine started pulling oil front injection bottle You need to Change ''Oil inject" solenoin from small manifold assy. Note:Green dot OR blue label denotes are oil injectoct ...
Question about Robinair Measuring Tools & Sensors
why will my robibair 34700z not inject oil You need to Rebuild/Replace oil injector solenoid, Located on "Inlet manifold block". Check attach picture to find location of oil injection solenoid. Hope ...
CANT PUMP NEW OIL IN First make sure that you are in a 28-30 inch vacuum. then if you are your oil inject solenoid is clogged up. when you take the covers off there is a small block with 5 solenoids ...
34788 will not inject oil You have to clean oil injector solenoid or replace the new one. To find oil injector solenoid (S3) in the manifold assy. see the attached picture marked with green arrow. ...
MY MACHINE WOULD NOT "INJECT OIL" INTO CUSTOMERS SYSTEM. OIL CANISTER IS 3/4 FULL WITH UNIVERSAL OIL/UV DYE. ALL PROCEDURES WERE FOLLOWED EXACTLY THE SAME AS ANY OTHER VEHICLE. FIRST TIME THIS HAS ...
Question about Robinair Measuring Tools & Sensors
347002k. wants to inject oil in charge mode? is it the check valve? You have to do Just following # Check oil drain solenoid for any debris or damage inside the solenoid flunger. Replace/rebuild as ...
Question about Robinair Measuring Tools & Sensors
I have a Robinair 347002K abnd cannot access anything under defaults. Defaults show as a menu item, but I can not see or select anything else under that heading I tried the 5454 password i saw on ...
Question about Robinair Measuring Tools & Sensors
have 34700z refrigerant pressure into oil injection bottle why? This is a normal function of the machin,so don't worry!
keeps telling me pressures too high to vaccuum, inject oil, leak test I can Recover,and fill please u tell me sokkia total station set 220k display error 205 Check wire and connection of vacuum ...